You maybe looking for:

Industry Portals

ZF28-420Type SF6 Gas Insulated Switchgear

ZF28-420 type GIS is composed of standard modules through flanged joint, which can meet the demand for substation optimization design through the flexible combination between modules.

Excellent performance

low operating cost

IEEE

IEC

Energy Storage

Power

Contact Us
product-img1.png

Proposition/Advantages

Technical Specifications

Proposition/Advantages

  • 01

    Outstanding GIS Layout

    The GIS phase spacing is 670mm and the standard spacing width is 2050mm (see layout). The whole interval of three-phase integrated transportation, its technological innovation level is domestic leading, international advanced level.

  • 02

    Convenient Maintenance

    Arrangement of circuit breaker is horizontal, it’s convenient for overhauling and emergency maintenance; it also will make lighter impact to the ground.

  • 03

    Low Insulation Discharge Level

    Excellent insulation level and low partial discharge. The only company in the industry that can achieve: under 1.2 times phase voltage (1.2×420/√3 = 291kV), the partial discharge of intervals is lower than 5pC, the partial discharge of the insulator is lower than 3pC.

  • 04

    Flange Double Ring Sealing

    Flange surface adopts double sealing ring structure, inner ring sealing gas, and its gas leakage rate is lower than IEC standard. Its outer ring prevents water and impurities from getting inside thus to improve safety and reliability.

Technical Specifications

Download

  • Rated voltage

    420 kV

  • Rated frequency

    50 Hz/60 Hz

  • Rated current

    4000 A

  • 1 min rated power frequency withstand voltage

    between open contacts: (650+165) kV between phases,to earth: 650 kV

  • Rated lightning impulse-resisting voltage peak (1.2/ 50μs)

    between open contacts Isolated fracture interval: (1425+240) kV between phases,to earth: 1425 kV

  • Rated short-circuit breaking current

    63 kA

  • Rated short-circuit making current

    171 kA

  • Rated short-time withstand current and duration

    63 kA / 3s

  • Rated peak withstand current

    171 kA