IES-321 Transformer Protection

IES-321 is designed specifically to protect various type of power transformers, including two-winding transformers, three-winding transformers as well as shunt reactors in 110kV voltage level and below. The device contains control measurement and monitoring functions. With its modular structure as well as flexible and powerful engineering tool, IES-321 offers future-oriented system solutions with high investment security and low operating costs.
The device is freely programmable. Functional logic diagrams can be developed with the use of graphical programming tool which also supports the configuration of binary inputs and outputs, analog inputs, control buttons, LEDs, disturbance recorder, event recorder, and user interface. Freely programmable logic makes it possible to modify typical functional logic diagrams considering a peculiar nature of the protected object. Three basic types of standard 19” case help to choose the most appropriate solution.

IEEE

IEC

Contact Us
03.png

Features

Technical Specifications

Features

  • 01

    Multiple Funtion

    Highly integrated functions. The main protection and backup protection can be configurated integrated and separately.


  • 02

    Advanced Principle

    Provides a variety of inrush current blocking methods. The self-adaptive blocking criterion makes the protection act quickly even when the no-load transformer is switched onto a slight fault.

  • 03

    High Sensitivity

    For single-phase ground fault inside the transformer, the zero-sequence differential protection has high sensitivity.

  • 04

    Widely Application

    The differential protection can be expanded up to 3 transformer sides. Any side can be taken as the reference side. With various corner modes, the transformer corner can be set flexibly.

Technical Specifications

Download

  • Standard

    IEC 60225-1: 2009

  • Dimensions (W×H×D)

    455×266.7×233.5mm(6U,without mounting bracket)
    221.3x266.7x233.5mm(6U 1/2,without mounting bracket)
    160.3x266.7x233.5mm(6U 1/3,without mounting bracket)

  • Mounting Way

    Flush mounted、semi-flush mounted、wall mounted、panel mounted

  • Material

    Stainless steel

  • Protection Class

    Front panel:IP54
    Side panel:IP40
    Rear panel:IP30

  • Communication Ports

    2 or 4 100Base-TX RJ45 Ethernet ports
    2 or 4 100Base-FX optical ports
    2 RS-485 serial ports for SCADA communication
    1 RS-485 serial port for clock synchronization
    1 front RJ45 port for debugging

  • Communication Protocol

    IEC 61850 Editions 1&2&2.1
    IEC 60870-5-103
    IEC 60870-5-104
    DNP3.0
    Modbus
    IEC 62439 Parallel Redundancy Protocol (PRP)
    IEC 62439 High-availability Seamless Redundancy (HSR)
    IEEE 802.1w Rapid Spanning Tree Protocol (RSTP)

  • Clock Synchronization

    IRIG-B: IRIG-B via serial port
    PPS: Pulse per second (PPS) via serial port or binary input
    IEEE 1588: Clock message based on IEEE 1588 via Ethernet network
    SNTP: Unicast (point-to-point) & broadcast SNTP mode via Ethernet network

  • Functions

    Transformer differential protection (87T)
    Inrush blocking
    CT saturation blocking
    Overexcitation blocking
    CT circuit failure blocking
    Amplitude compensation
    Phase angle compensation
    Reactor differential protection (87R)
    Restricted earth-fault protection (64REF)
    Phase overcurrent protection (50/51P)
    Earth-fault protection (50/51G)