IEC
IES-5301 Gateway
The IES-5301 is a front-end access device designed for substation applications. It serves as the core node for unified data acquisition, protocol conversion, and communication management within the substation monitoring system, enabling reliable interconnection between various intelligent electronic devices (IEDs) in the station and the upper-level monitoring system. The IES-5301 supports several protocols, such as IEC 61850,IEC 60870-5-101/104, IEC 60870-5-103, Modbus and DNP3.0. Data can be transmitted to and received from analog channel, digital channel or network connected to CC, DCS or other system. The direct transmission mode and the device independent avoid any interaction or influence with the substation SCADA (Supervisory Control And Data Acquisition) system.
-
Multiple Protocols
-
Multiple Languages
-
Engineered for Broad Deployment
-
Flexible Networking
Product Highlights
Multiple Protocols
The IES-5301 gateway supports mainstream protocols (IEC 61850, IEC 60870-5-101/104, Modbus, DNP3), unifies access to various substation devices, aggregates multi-vendor multi-protocol data, standardizes it via protocol conversion, and uploads it to the station-level monitoring system.
Multiple Languages
The device management interface and logs support multi-language switching, facilitating localized operation by foreign maintenance personnel.
Engineered for Broad Deployment
Adopts a wide temperature and voltage design to adapt to the varying requirements of different overseas regions.
Flexible Networking
Supports multiple network topologies including star, ring, and bus, accommodating the networking requirements of substations of varying scales.
Technical Specification
Appearance & Structure
2U chassis, aluminum enclosure, silver-gray color, IP20 protection rating, grounding bolt diameter ≥ 6mm.
Power Supply
220V/110V DC dual power supply, supporting DC3 level (deviation: -20% to +15%).
Power Consumption
≤ 50W (measured: 20.83W).
Timekeeping Performance
Without external clock source correction, 24-hour timekeeping error ≤ 1s (measured: 129.1ms).
Time Synchronization Performance:
IRIG-B synchronization accuracy ≤ 1ms (measured: 0.40ms); SNTP synchronization accuracy ≤ 100ms.
Environmental Adaptability
-40°C to +70°C (for LCD: -20°C to +55°C).
Insulation Performance:
Power circuit to ground insulation resistance ≥ 5 MΩ (measured: >21.29 GΩ); communication interface to ground insulation resistance ≥ 5 MΩ (measured: >21.29 GΩ).
Dielectric Strength
Power circuit to ground: 1500V applied with no breakdown or flashover; communication interface to ground: 500V applied with no breakdown or flashover.
Impulse Voltage
After applying ±5kV, 1.2/50μs standard lightning impulse to power input ports, data transmission remains normal.
Electromagnetic Compatibility (EMC)
Passed multiple immunity tests including oscillatory waves, electrical fast transients/bursts, electrostatic discharge, power frequency magnetic field, pulse magnetic field, damped oscillatory magnetic field, radio-frequency electromagnetic field radiation, RF conducted disturbances, surge (shock), and voltage dips and short interruptions.