IEC
GB
Grid-Forming STATCOM
With cascaded H-bridge topology, optimized component capacity and advanced grid-forming control, GFM STATCOM serves weak grids and renewable energy stations.
-
True Grid-Forming
-
Engineered for Long-Term Reliability
-
Flexible Delivery
-
Simplified O&M
Product Highlights
True Grid-Forming
Zero-delay voltage source characteristic, active grid support, and self-adaptation for both strong and weak power grids.
Engineered for Long-Term Reliability
Full-lifecycle high-reliability design, with annual equipment availability of 99.7%.
Flexible Delivery
Modular and standardized design, with a shortest delivery cycle of 30 days.
Simplified O&M
Intelligent early warning of faults and fast & accurate fault location.
Technical Specification
1 - Rated Voltage(PCC)
66kV~750kV
2 - Rated Voltage(POC)
10kV~ 66kV
3 - Rated Capacity
5MVAr~450MVAr
4 - Overload Capacity
1-3pu@10s; Supports customized design
5 - Rated Frequency
50Hz/60Hz
6 - Topology
MMC
7 - Connection Mode
Star connection/ Delta connection
8 - Cooling Method
Water cooling
9 - Operation Modes
Grid Forming/Grid Following
10 - Installation Method
Indoor/ Outdoor
11 - Operating Temperature
-45℃ ~ 50℃, configurable according to local climate conditions
12 - Altitude
5000m